Anandha Jothi Industries
Anandha Jothi Industries
Chennai, Tamil Nadu
Our Products

Micro OHM Meter

MICRO OHM METER    0 – 100 Amps

Sl No.

Description

Data

1

Input

230 V AC,50 Hz Single Phase

2

Output Current

0-100Amps DC Maximum

3

Current Selection

Selection through Variable (Variac)

4

Capacity

700 VA Max. Output Current.

5

Duty Cycle

3min ON / 5min OFF

6

Volt meter

0-200mV Direct Reading  Digital D.C Mill voltmeter

Provided Press to read push button

7

Ammeter

0-100A D.C Direct Reading digital Ammeter

8

Panel Comprising of

 A )Out put ON / OFF Push Button Controls 

B) Mains Fuse Indication

c) Control Fuses for Protection & Indication

d) Output Current / Input Milli volt terminals

Secondary Injection Kit 40 A
Portable over Current Relay Test KIT - Unit – I

S.No.ModelRLY – 786
1SUPPLY VOLTAGE230 Volts , 50 Hz, (± 10%), AC Single Phase supply through Toggle switch & Control Fuse for Units 1 & 2.
2OUTPUT1. Variable current Application 0 – 40A AC
2. For voltage, the Variac output is connected to variable voltage output 0 – 230 V AC with fuse.
3. Separate current output terminals and separate voltage output terminals are provided
(At one time either current or voltage circuit will be connected through a Toggle Switch)
3CONTROLS1. 1ST Unit with Push Button Control Only. When the ON/OFF push button is operated, all outputs will be connected to the output connectors
2. 2nd unit with Push Button Control & By-Pass Switch
4CURRENT OUTPUTOutput : 0 – 40A – 25A – 10A - 5A – 1A
Each of these outputs has a separate terminal referred to one common terminal.
Each current output terminal is for 400 VA capacity, except 1A output which is for 250 VA capacity
5VOLTAGE OUTPUT0-230 V AC / 2A – Variable voltage output through fuse units,Separate pair of test terminals is provided
6RATINGContinuous (3min ON / 10 Min. OFF)
7AMMETER3 ½ Digit, 12mm LED type. Accuracy: ± 1% (Direct reading 0 – 40 A)
For current ranges of 1A, 5A, 10A, 25A and 40A AC, readings can be noted directly from the digital ammeter.
8VOLTMETER3 ½ Digit, 12mm LED type. Accuracy:± 1 % (Common meter for measurement of Unit-1 & Unit-2 AC & Unit-2 DC output through a 3 position selector switch)
a. an be read at a time.
CT Tester
Checking the Polarity of Current Transformers The Polarity of current transformers is extremely important. Just like a battery, a current transformer too has a polarity. The polarity determines the direction of the secondary current in relation to the primary current, Wrong connection of the current transformers can cause false operation of the protection relays. Hence, it is vital to ensure that the current transformers are connected with the correct polarity.

C.T Polarity Tester
Checking the Polarity of Current Transformers

The Polarity of current transformers is extremely important. Just like a battery, a current transformer too has a polarity. The polarity determines the direction of the secondary current in relation to the primary current.

Wrong connection of the current transformers can cause false operation of the protection relays. Hence, it is vital to ensure that the current transformers are connected with the correct polarity.

A DC source is connected with the positive terminal to P1 and the negative terminal to P2. An analog voltmeter is connected to the secondary terminal of the CT. The positive terminal of the meter is connected to terminal S1 of the CT while the negative is connected to terminal S2.

A contact is momentarily made through the switch. The contact is made for a second and broken. This is important as continuous contact can short-circuit the battery. The momentary make-break contact causes a deflection in the analog multimeter in the positive direction, if the polarity is correct.

If the deflection is negative, it indicates that the polarity of the current transformer is reversed. The terminals S1 and S2 need to be reversed and the test can be carried out.

Hi Pot Kit

Sl No.

Description

Data

1

Input

For all Models

230V/ A.C / 50Hz, Single Phase 

Output

MODELS 

Size & Weight

2

0 - 30 KV AC / 50 mA & 40 KV DC / 25mA 

HV – 30 KV

Tr: 13.5”x11.5”x8.5”/ Wt: 25 kgs .Appx C.Unit : 13.5”x11.5”x8.5”/ Wt: 12 kgs .Appx

0 - 60 KV AC / 50 mA & 75 KV DC / 25mA 

HV – 60 KV

Tr: 18”x18”x12”/ Wt: 41 kgs .Appx C.Unit : 13.5”x11.5”x8.5”/ Wt: 14 kgs .Appx

0 - 70 KV AC / 50mA & 80 KV DC / 25mA

HV – 70 KV

Tr: 18”x18”x12”/ Wt: 45 kgs .Appx C.Unit : 13.5”x11.5”x8.5”/ Wt: 15 kgs .Appx

Hi Pot Kit

Sl No.

Description

Data



0 - 70 KV AC / 50mA  &                               80 KV DC / 25mA

HV – 70 KV

Tr: 18”x18”x12”/ Wt: 45 kgs .Appx                C.Unit : 13.5”x11.5”x8.5”/ Wt: 15 kgs .Appx               

0 - 30 KV AC / 100 mA &                             40 KV DC / 25mA

HV – 30 KV (C)

Tr: 16”x14”x13”/ Wt: 40 kgs .Appx                C.Unit : 17”x13”x9.5”/ Wt: 15 kgs .Appx               

Hi Pot Kit

4a

Protection : HV Over Current Tripping  Selection        - A.C                                                      

10 mA/25 mA & 50 mA AC

25mA / 50mA / 75mA &100mA AC

Relay Test Kit 100A

We offer extensive range of Secondary Injection Kit s RLY-108 Models which are suitable for carrying-out the tests in Electro Magnet and Numerical Relays like (Multifunction Numerical Relays of ABB, EE /Areva, Siemens, SEL, L&T, GE, Argus & Easun-Reyrolle Makes Relays )


Features:

  • Single Kit with two units

  • Two separate inputs, five outputs

  • Test outputs available:

unit – I : 0 to100 A AC, 0 to 240 volts AC

unit – II: 0 to1 A AC, 0 to 240

  • volts AC and aux 0 to 240 volts DC
  • Panel with clear and easy to follow legend.
  • Built in Timer for testing IDMT relays or circuit breakers.
  • Overload protection.
  • Independent Digital readouts of current, voltage and time.

The kits can be for all types of relays (current and voltage relays) except MOH & Distance relays


Applications:

Suitable for checking protective devices such as all types of relays:

  • Over current relay
  • IDMT over current relay,
  • Under current relay,
  • Earth fault relay,
  • Over Voltage relay.
  • Under voltage relay,
  • Differential relay,
  • Negative sequence relay,
  • Motor protection relay,
  • Auxilary relay,
  • Thermal relay,
  • Time delay relay.
  • Single Pole circuit Breaker timing and meters on installation and at regular services.

Quick detection of faulty or incorrectly adjusted devices during routine current/voltage injection tests. Built in timer to measure the operating time.

 

Welcome to Anandha Jothi Industries

Manufactured using quality material, these Electrical & Electronic Testing Equipment are extensively used in the Power industry and are capable of catering to the testing needs of varied processes. Further, the strict quality testing and checks followed by us during the manufacturing process also assures of high operational efficiency as well as longer working life of our range of equipment.



The product range we are offering includes DC Power Pack, Oil Test Kit, Ct Knee Point Voltage Tester, Frequency Cum Voltage Generator, Primary Injection Kit, Contact Resistance Meter, Circuit Breaker Time Interval, Energy Meter Test Kit, Portable Over Current Relay Test Kit and HV Test Kit AC/DC.



Read More...
 

Contact Us:
 

 

Anandha Jothi Industries
Mr. Mahendran .  (Manager)
No. 3/3, Viswanathan, 3rd Cross Street, Dharmaraja Nagar, Karambakkam